Fire Safety Technology Background
Back to Solutions
Fire Safety

Fire Safety &
Inertisation Systems.

Coal mills, silos, and dust-handling equipment are constant fire risks. Our systems use CO2, Nitrogen, or Inert Gas to automatically prevent and control fires.

CO₂ Inertisation Systems

High & low pressure CO₂ for coal mills and silos.

Fully automated fire suppression systems designed to NFPA 12 standards. Available in high‑pressure cylinder batteries or low‑pressure refrigerated tank configurations.

High Pressure: Stored at 60 kg/cm²
Low Pressure: Stored at 300 psi (-18 °C)
Fully automated with BMS integration
Automatic purging on high temp/CO signals
Non‑conducting and safe for electrical systems

Technical Specifications

ComplianceNFPA 12 Guidelines
System TypeTotal Flooding / Local Application
ActivationAutomatic / Semi‑Automatic / Manual
MonitoringContinuous weight/level monitoring

PSA Nitrogen Generator Systems

On‑site nitrogen generation for continuous inerting.

Generate nitrogen on‑site from atmospheric air using Pressure Swing Adsorption (PSA) technology. Eliminates cylinder dependency and logistics.

Carbon Molecular Sieves from Japan Enviro Chemicals
Purity from 99% to 99.99%
Skid‑mounted compact unit
Low power consumption

Technical Specifications

Capacity5 Nm³/hr to 2 000 Nm³/hr
Purity99% – 99.99%
Dew Point-60 °C NTP
PressureCustomisable

Inert Gas Generator Systems

Independent inert gas generation for remote locations.

Ideal for remote locations where CO₂ refilling is impractical. Generates inert gas (CO₂ + Nitrogen) through stoichiometric combustion of fuel.

Eliminates external gas supply dependency
Low capital and utility cost vs CO₂
Automatic/Semi‑automatic operation
Oxygen content < 1%

Technical Specifications

Capacity50 – 500 Nm³/hr
Oxygen Content< 1%
CO Content< 200 ppm
FuelLiquid or gaseous